Features

    • Can provide up to 2 hours fire resistance on proprietary fire doors
    • Non compliant fire doors can be salvaged
    • Cost-effective solution
    • Easy retro-fit installation
    • Flame retardant PVC top hat section, encapsulating a high performance intumescent material and two rows of aggressive self adhesive tape.
    • Ideal for fire engineered solutions where extra protection is necessary for life safety.

Applications

    Intumescent retro-fit seal for upgrading door perimeter gaps where the clearance exceeds the maximum 3mm specified by AS1905/1. Used to upgrade existing fire doors with up to and including 6mm perimeter gaps.

    Approvals:

    • Fire tested to AS/1530 Part 4 for up to 2 hours on proprietary fire door assemblies in accordance with AS1905 Part 1


Specifications

Flame retardant PVC

PRODUCT CODEFDUSKG4002-2100mm
MATERIAL
GAP SIZEUp to and including 6mm perimeter gaps.
SIZESDimensions: 38mm x 1.6mm
FINISHStandard Colour: White and Silver
Can be painted on-site
FIXINGThe KG4002 intumescent seal is simply applied to the top and sides of the door frame with two rows of aggressive self-adhesive tape. No screw fixing required.